neiye1

OEM manufacturer Terminal Protection Electrical Appliance - T1 Level Surge Backup Protector ZGLEDUN LDSCB-12.5/5/25/50 Series, SPD Surge Protective Device, T1 Level Lightning Protection – Elemro

Short Description:


Product Detail

Product Tags

Related Video

Feedback (2)

It truly is our responsibility to fulfill your requirements and successfully provide you. Your fulfillment is our best reward. We're seeking forward in your check out for joint development for Miniature Circuit Breaker 32a, Residual Current Devices, Oem Electrical Product, We will make greater efforts to help domestic and international buyers, and create the mutual benefit and win-win partnership between us. we are eagerly waiting for your sincerely cooperation.
OEM manufacturer Terminal Protection Electrical Appliance - T1 Level Surge Backup Protector ZGLEDUN LDSCB-12.5/5/25/50 Series, SPD Surge Protective Device, T1 Level Lightning Protection – Elemro Detail:

Product Description:

The ZGLEDUN LDSCB series product is a SPD dedicated surge backup protector. It can effectively solve the fire hazard caused by the deterioration of the lightning protector and the power grid failure, and solve the failure of the lightning protector caused by the malfunction of the backup protection device caused by lightning. This backup surge protector ensures that the surge protector (SPD) does not catch fire, and the equipment lightning protection continues to be effective. At present, fuses or circuit breakers are widely used in coordination with SPD. When SPD fails or short-circuits, it will cause fire. Seies LDSCB is specially designed for SPD. It will not break under a large lightning strike. But it can be quickly broken when small power frequency current occurs after SPD failure. 

Features:

◆SCB can achieve selective breaking of the passed power frequency current and lightning current, which can effectively protect the SPD surge protector due to deterioration that causes the SPD start voltage to drop below the power supply voltage, and the power frequency leakage current increases, causing serious fire accidents.

◆ When the SPD has lightning current passing through, the SGB connected in series at the front of the SPD can ensure that the lightning current will not trip, damage, and the lightning protection will continue to be effective;

◆The UP Value (voltage protection level value) of SCB is very low when passing thunder current;

◆Using parameter control trip mechanism, and installation with 35mm guide rail .

 

Main Technical Parameters
Model LDSCB-A12.5 LDSCB-A15 LDSCB-A25 LDSCB-A50
Non-tripping Shock Wave le 12.5kA(10/350μs) 15kA(10/350μs) 25kA(10/350μs) 50kA(10/350μs)
Residual Pressure Up < 1000V < 1000V < 1500V < 1500V
Rated Operational Voltage Ue 120V/230V/400V AC
Residual Pressure Up 20kA(8/20μs) < 300V
Current Trip Value lo (Instantaneous) 2A±5%(2~5A) Optional
Power Frequency Load Current Breaking Time (To) < 0.1s
Power Frequency Current Delay Trip 500mA-3A Optional Current (is not standard and selected by the customer )
Power Frequency Current Delay Trip Time 1s~120s Optional Time (is not standard and selected by the customer)
Test Button Verification of the tripping system (once a month)
Shell Protection Level IP20
Crimping Screw M6
Installation Location Installed on front of SPD
Connecting Wire Section 4-16mm2
Protection Action Due to Ambient Temperature Switch between -25℃ and +60℃
Storage Environment Temperature -40℃~75℃ Relative humidity <95% (below 25℃)
Working Environment  Temperature -25℃-60℃ Relative humidity <95% (below 25℃)

 Measurements Wiring

Main Structure and Working Principle:

This SPD with one-port, anti-shock protection function, indoor fixed installation, and of voltage limited type.

SPD has a built-in disconnector. When the SPD fails due to overheating or breakdown, the disconnector can automatically disconnect it from the grid and give an indication signal at the same time. The visible indicator is white when the SPD is working normally, and is red when it fails to disengage.

IP+N, 2P+N, and 3P+N are respectively composed of SPD+NPE zero-ground protection modules of IP, 2P, and 3P, which are used in power supply systems such as TT and TN-S.


Product detail pictures:

OEM manufacturer Terminal Protection Electrical Appliance - T1 Level Surge Backup Protector ZGLEDUN LDSCB-12.5/5/25/50 Series, SPD Surge Protective Device, T1 Level Lightning Protection – Elemro detail pictures


Related Product Guide:

"Control the standard by the details, show the toughness by quality". Our firm has strived to establish a highly efficient and stable workers workforce and explored an effective high-quality management system for OEM manufacturer Terminal Protection Electrical Appliance - T1 Level Surge Backup Protector ZGLEDUN LDSCB-12.5/5/25/50 Series, SPD Surge Protective Device, T1 Level Lightning Protection – Elemro , The product will supply to all over the world, such as: Monaco, Seychelles, Colombia, Since its foundation , the company keeps living up to the belief of "honest selling , best quality , people-orientation and benefits to customers. " We're doing everything to supply our customers with best services and best solutions . We promise that we are going to be responsible all the way to the end once our services begin.
  • We are really happy to find such a manufacturer that ensuring product quality at the same time the price is very cheap.
    5 Stars By Albert from Madagascar - 2017.06.19 13:51
    This is the first business after our company establish, products and services are very satisfying, we have a good start, we hope to cooperate continuous in the future!
    5 Stars By Christine from Vietnam - 2017.06.25 12:48
    Write your message here and send it to us