The basic function of the fire-fighting equipment power status monitor is to monitor the power supply of the fire-fighting equipment. It should be ensured that the working status of the power supply of the entire fire-fighting system can be displayed in real time on the fire-fighting equipment power status monitor or in the fire control room. The Leidun fire equipment power status monitor is developed according to the Chinese national standard GB28184-2011. It is a real-time monitoring of the power supply of the fire equipment. By checking the parameters such as the voltage/current value and switch status of the power supply of the fire equipment, it can judge whether the power equipment exists. The fault information of overvoltage, undervoltage, overload, phase loss, and error is transmitted to the monitoring host installed in the fire control center through the second bus. Real-time display of alarm information, address and other information, and active storage of alarm information, so as to achieve the role of pre-turtle, escort the normal operation of the fire equipment power supply.
The main technical parameters:

 

  • Working power: AC20V, 50Hz
  • Output voltage: DC24V
  • Communication method: two bus communication
  • Communication distance: ≤1000m (extendable)
  • Equipment capacity: 4 loops in total, 32 address points per loop
  • Display mode: 10.2-inch high-definition touch screen (full Chinese display)
  • Ambient temperature: -10℃~ +40℃
  • Storage temperature: -40℃~ +75℃
  • Relative humidity: 5%~95%, no condensation
  • Communication line: NH-RVS-2×2.5mm² copper core twisted pair
  • Protection class: IP30
  • Installation method: wall-mounted
  • Dimensions: 550mm×400mm×200mm

 