neiye1

ABB ACB Emax2 E1.2B 630 Ekip Dip Ll 3P FF 1SDA070701R1

Short Description:

Extended Product Type: E1.2B 630 Ekip Dip LI 3p F F
Product ID: 1SDA070701R1
EAN: 8015644745516
Catalog Description: E1.2B 630 Ekip Dip LI 3p F F

Long Description: C.BREAKER SACE EMAX2 E1.2B 630 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP/DIP-LI R 630 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED

  • Promotion Price: 1498.53USD
  • Stock Qty: 1pcs
  • Lead Time: 3-4Weeks
  • Product Detail

    Warranty Period

    How to Buy

    Product Tags

    Circular Value

    Circular Design Principles Recyclability Rate:
    Design for Closing Resource Loops – Standard EN45555 – 76.4 %
    Conflict Minerals Reporting Template (CMRT):
    End of Life Instructions:
    Group Waste to Landfill Target:
    UL 2799 Zero Waste To Landfill Validation available
    Toxic Substances Control Act – TSCA:

    Eco Transparency

    Environmental Product Declaration – EPD:

    Environmental

    Environmental Information:
    REACH Declaration:
    RoHS Information:
    RoHS Status:
    Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
    SCIP:
    5db9272f-d385-4a4a-a0e6-73274e7613b2 China (CN)

    Ordering

    Order Code US and Canada:
    Z1BNEEBA000A000000XX
    EAN:
    8015644745516
    Minimum Order Quantity:
    1 piece
    Customs Tariff Number:
    85362090

    Dimensions

    Product Net Width:
    210 mm
    Product Net Height:
    296 mm
    Product Net Depth / Length:
    183 mm
    Product Net Weight:
    14 kg

    Container Information

    Package Level 1 Units:
    box 1 piece
    Package Level 1 Width:
    270 mm
    Package Level 1 Height:
    350 mm
    Package Level 1 Depth / Length:
    330 mm
    Package Level 1 Gross Weight:
    16 kg
    Package Level 1 EAN:
    8015644745516

    Additional Information

    Current Type:
    AC
    Electrical Durability:
    Ue =< 440 V 8000 cycle
    Ue = 500 … 690 V 8000 cycle
    30 cycles per hour
    Mechanical Durability:
    20000 cycle
    60 cycles per hour
    Number of Poles:
    3
    Power Loss:
    31 W
    Product Main Type:
    SACE Emax 2
    Product Name:
    Air Circuit Breaker
    Product Type:
    Air Circuit Breaker
    Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics):
    100 %
    Rated Current (In):
    630 A
    Rated Voltage (Ur):
    690 V
    Rated Impulse Withstand Voltage (Uimp):
    acc. to IEC 60947-2 12 kV
    Rated Insulation Voltage (Ui):
    AC 1000 V
    Rated Operational Voltage:
    690 V AC
    Rated Service Short-Circuit Breaking Capacity (Ics):
    (220 V AC) 42 kA
    (230 V AC) 42 kA
    (380 V AC) 42 kA
    (400 V AC) 42 kA
    (415 V AC) 42 kA
    (440 V AC) 42 kA
    (500 V AC) 42 kA
    (660 V AC) 42 kA
    (690 V AC) 42 kA
    Rated Short-time Withstand Current Low Voltage (Icw):
    for 1 s 42 kA
    for 3 s 24 kA
    Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (400 V AC) 42 kA
    (415 V AC) 42 kA
    (440 V AC) 42 kA
    (500 V AC) 42 kA
    (525 V AC) 42 kA
    (690 V AC) 42 kA
    Rated Uninterrupted Current (Iu):
    630 A
    Recommended Screw Driver:
    Main Circuit M10
    Release:
    Ekip Dip LI
    Release Type:
    EL
    Short-Circuit Performance Level:
    B
    Standards:
    IEC
    Sub-type:
    E1.2
    Terminal Connection Type:
    Front
    Terminal Type:
    Bolt
    Tightening Torque:
    45 N·m
    Version:
    F
    CAD Dimensional Drawing:

    Certificates and Declarations

    ATEX Certificate:
    CSA Certificate:
    CSA Certificate (Intrinsic Safe):
    Data Sheet, Technical Information:
    Declaration of Conformity – CE:
    UL Certificate:
    VDE Certificate:
    Mechanical Drawings:
    Wiring Diagram:
    Instructions and Manuals:

    Classifications

    ETIM 7:
    EC000228 – Power circuit-breaker for trafo/generator/installation protection
    ETIM 8:
    EC000228 – Power circuit-breaker for trafo/generator/installation protection
    ETIM 9:
    EC000228 – Power circuit-breaker for trafo/generator/installation protection
    IDEA Granular Category Code (IGCC):
    4926 >> Air circuit breakers
    Object Classification Code: Q
    UNSPSC  : 39121615
    WEEE Category:5. Small Equipment (No External Dimension More Than 50 cm)
    eClass:V11.1 : 27370409

  • Previous:
  • Next:

  • 1. Most of new products are guaranteed for 12 months from the date of delivery, some for 18 months;
    2. All products sent for repair shall be guaranteed for 6 months after repair;
    3. Paid repair service can be provided for products beyond the warranty period.

    There Are Three Ways to Contact ELEMRO to Place  Orders

    1. You can proactively contact ELEMRO through social media apps such as WhatsApp, Skype, Viber, and Facebook:

    ELEMRO WhatsApp

    ELEMRO Skype

    ELEMRO Viber

    2. You can fill in your requirements in the bottom right corner of the webpage, and we will contact you as soon as we receive the requirements;
    3. You can also contact various ELEMRO offices for offline communication and cooperation. Click here for ELEMRO office information.

    Write your message here and send it to us